Turn it down on cold nights
The guideline drops with the outdoor temperature. A humidistat set to 40% in November can soak the windows in a January cold snap.
Home comfort & condensation
Conclusion: Keep indoor humidity at or below 40% when it's 20–40°F outside, and about 5 points lower for every 10°F colder (35% at 10–20°F, 30% at 0–10°F, 25% at −10–0°F). Above that, ordinary windows start to sweat. Enter today's temperature to check your home.
Winter humidity guideline (about 70°F indoors)
| Outdoor temp | Max indoor RH | Indoor dew point |
|---|---|---|
| 20 to 40°F | 40% | 44.6°F |
| 10 to 20°F | 35% | 41.1°F |
| 0 to 10°F | 30% | 37.1°F |
| −10 to 0°F | 25% | 32.6°F |
| −20 to −10°F | 20% | 27.1°F |
Guideline: Minnesota Center for Energy & Environment; same steps in the ASHRAE-based table the EPA reprints. Dew points computed at 70°F.
Humidity & window fog check
Keep indoor humidity at or below
Enter temperatures to see your target.
Assumptions appear here after a valid calculation.
Window type matters
Indoor air at 70°F. Each cell is the relative humidity whose dew point equals the estimated inner-glass temperature. Edges, frames and window corners are colder than the center, so condensation shows there first — treat these as ceilings, not targets.
| Outdoor | Guideline max | Single pane | Double clear | Double low-E | Triple low-E |
|---|---|---|---|---|---|
| 30°F | 40% | 36% | 63% | 77% | 85% |
| 20°F | 40% | 27% | 56% | 72% | 82% |
| 10°F | 35% | 20% | 50% | 68% | 79% |
| 0°F | 30% | 15% | 44% | 64% | 75% |
| −10°F | 25% | 11% | 39% | 59% | 72% |
| −20°F | 20% | 8% | 34% | 56% | 69% |
Glass temperature = indoor − (U ÷ 1.46) × (indoor − outdoor), using an interior surface film of 1.46 Btu/h·ft²·°F and U-factors 1.04 / 0.48 / 0.27 / 0.17. Single-pane glass explains why older homes need storm windows or film to hold even 25–30% humidity.
Size a humidifier
Cold outdoor air that leaks in carries very little water. Once it warms to room temperature it is very dry, so a humidifier has to make up the difference. This uses the outdoor temperature and indoor temperature from the calculator above.
—
| Home size (8 ft ceilings) | Tight (0.35 ACH) | Average (0.5 ACH) | Leaky (1.0 ACH) |
|---|---|---|---|
| 1,000 sq ft | 2.8 gal/day | 4.0 gal/day | 7.9 gal/day |
| 1,500 sq ft | 4.2 gal/day | 6.0 gal/day | 11.9 gal/day |
| 2,000 sq ft | 5.6 gal/day | 7.9 gal/day | 15.9 gal/day |
| 2,500 sq ft | 6.9 gal/day | 9.9 gal/day | 19.8 gal/day |
| 3,000 sq ft | 8.3 gal/day | 11.9 gal/day | 23.8 gal/day |
dry air (lb/h) = floor area × ceiling × ACH × 0.075
water (lb/h) = dry air × (Windoor − Woutdoor)
gallons/day = water × 24 ÷ 8.34
W is the humidity ratio (lb water per lb dry air) = 0.622 × pv ÷ (14.696 − pv), with vapor pressure from the Magnus formula. Leakage rates are rough presets; a blower-door test gives your real number.
Too dry vs too humid
| Too dry (below ~30%) | Too humid for the weather | |
|---|---|---|
| What you notice | Static shocks, dry skin and lips, scratchy nose and throat | Water or frost on the inside of windows, damp sills, musty smell |
| House effects | Gaps in wood floors and trim, loose furniture joints | Peeling paint, mold on sills and cold exterior-wall corners, rot over time |
| Fix | Humidifier up to the target above; seal air leaks (less dry air comes in) | Lower the humidistat, run bath/kitchen fans, vent the dryer outside, add storm windows or film |
The guideline drops with the outdoor temperature. A humidistat set to 40% in November can soak the windows in a January cold snap.
A $10–20 digital hygrometer is enough. Check it near the middle of the house, away from the shower, kettle and humidifier.
Open blinds and curtains at night so room air reaches the glass; storm windows or interior shrink film raise the glass temperature a lot.
Common questions
Lower than in summer, and lower the colder it gets: no more than 40% at 20–40°F outside, 35% at 10–20°F, 30% at 0–10°F, 25% at −10–0°F, 20% at −20 to −10°F and 15% below −20°F. Above about 40°F outside, the EPA's ideal 30–50% range applies.
The inside of the glass is colder than the room. When it drops below the air's dew point, water condenses on it (frost if the glass is below 32°F). Colder weather, less-insulating glass and higher humidity all make it worse; edges and frames go first.
Usually, in cold climates. At 70°F and 50% the dew point is about 50.5°F, and the center of clear double-pane glass is about 50°F when it is 10°F outside — so it sweats. UMN Extension says moisture problems may occur above 50%.
It is the bottom of the EPA's 30–50% ideal range and the guideline maximum at 0–10°F outside. NDSU Extension notes that below about 30% skin dries and nasal passages get irritated, so 30% is a sensible cold-weather compromise.
About 7.9 gallons a day for a 2,000 sq ft, 8 ft ceiling home at 0.5 air changes per hour holding 40% at 70°F when it is 20°F outside; about 5.6 for a tight house. Use the humidifier tool for your home.
Yes — their inner glass stays warmer. At 20°F outside the center of low-E double glass fogs around 72% versus 56% for clear double and 27% for single pane. Edges are colder, so stay at the guideline anyway.
A little, in your favor. With clear double-pane glass and 20°F outside, the center of the pane fogs at about 59% when the room is 65°F versus 56% at 70°F, because cooler air holds less water at the same RH. Try both in the calculator.
Planning estimate only. Real glass, frame and wall temperatures vary with wind, sun, curtains and window age. If you see condensation, lower humidity regardless of the number shown. Persistent mold or moisture problems need a building professional.
Last updated: 2026-10-18. Vapor pressure: Magnus formula (Alduchov & Eskridge, 1996). Independent tool — not affiliated with any agency, window or humidifier brand.